© 2016. RCB Chemicals & Services. All rights reserved.
PERFORMANCE:
BAC - 200™ offers a variety of critical performance and application benefits:
Powerful inhibitor against a variety of carbonate and sulfate scale:
Instructions for
use
|
PRODUCT DESCRIPTION:
BAC-200™ is an aqueous solution of hydrazine, developed to prevent corrosion in boilers and heating systems by reacting with dissolved oxygen to form harmless nitrogen and water.
DOSING and CONTROL:
BAC-200™ must be fed continuously by the chemical feed pump to the earliest point possible in the feedwater system. Any interruption in the feed will result in corrosion of the preboiler and boiler system and possible tube failure. BAC-200™ can be fed neat or diluted. Closed systems should be used for dosing and for transferring from one container to another. To prepare a dilute solution (usually between 1:10 and 1:100) use condensate or demineralized water at temperature between 10 and 37.8˚C to avoid odor formation.
DOSAGE CALCULATION:
BAC-200™ dosage will be the sum of the requirements for reaction with dissolved oxygen plus the desired residual.
BAC-200™ dosage (ppm)
= feedwater ppm O2 x 2.85+0.5. Sampling and Testing BAC-200™ programs should be monitored and controlled using suitable test methods.
SPECIFICATIONS |
|
Appearance |
Colorless liquid |
pH |
<12 |
Specific Gravity @20˚C |
1.02-1.04g/cm3 |
Freezing Point |
-65˚C |
Odor |
Ammonical |
Packaging Formats |
Pakistan |
Can |
25 Kg |